Phase Unbalance, Loss, Under Voltage Relays/ATC Diversified/ ATC Diversified SLC Series – Phase Unbalance and Loss Monitor
share this itemATC Diversified SLC Series – Phase Unbalance and Loss Monitor
The SLC Series is designed to protect 3-phase equipment against Phase Unbalance and Phase Loss conditions.
With normal operating voltages applied to all three phases, the internal relay will remain de-energized (DROPPED-OUT).
When a Phase Loss or Phase Unbalance exceeding the pre-selected trip point occurs, the relay will energize (PICK-UP). The SLC series is typically used in conjunction with a shunt trip breaker.
Both Delta and Wye systems may be monitored. In Wye systems, connections to neutral are not required. NOTE: When a phase is lost while the motor is running, a condition known as regeneration occurs where a voltage is induced into the open phase nearly equal in magnitude to the normal phase-to-phase voltage. The SLC series is designed to detect this condition when properly adjusted.
View the PDF Datasheet for ATC Diversified SLC Series – Phase Unbalance and Loss Monitor Relays -or-
**View the complete list of ATC Diversified Part Numbers carried by Universal Electronic Supply**