Phase Unbalance, Loss, Under Voltage Relays/ATC Diversified/ ATC Diversified SLE Series – Phase Unbalance, Loss, Under Voltage Relays
share this itemATC Diversified SLE Series – Phase Unbalance, Loss, Under Voltage Relays
The SLE Series is designed to protect three-phase equipment against Phase Unbalance, Phase Loss, and Under Voltage.
With normal operating voltage present on all three phases, the internal relay will energize (PICK-UP). When a phase loss occurs or the voltages fall outside the preset unbalance or under voltage settings, the internal relay will de-energize (DROP-OUT). The relay automatically resets when the line conditions return to normal. Both Delta and Wye systems may be monitored. In Wye Systems, connections to neutral are not required.
NOTE: When a phase is lost while the motor is running, a condition known as regeneration occurs where a voltage is induced into the open phase nearly equal in magnitude to the normal phase-to-phase voltage. The SLE series is designed to detect this condition when properly adjusted.
View the PDF Datasheet for ATC Diversified SLE Series – Phase Unbalance, Loss, Under Voltage Relays -or-
**View the complete list of ATC Diversified Part Numbers carried by Universal Electronic Supply**